Languages

Transformer electric pumps

These pumps are designed to create circulation of transformer oil in the cooling systems of power transformers of main line electric locomotives (TT) and stationary power transformers of electric power plants (TE, MT). Features: mono-block pumps with oil-flooded stator (TT and MT) and bush stator (ТA).

1
2
3
4
5
6
7
8
ТТ 63-10
63
10
2,2
3,5
4
840
85
МТ 16-10
16
10
1,1
4,0
4
840
85
2ТA 100-8
100
8
3,5
5,0
4
840
80
1ТA 100-15
100
15
7,5
5,0
4
840
80
1ТA 100-20
100
20
7,5
5,0
4
840
80
6ТA 160-10
160
10
5,5
5,0
4
840
80
1 - Designation of electric pump; 2 - Flow, m3/h; 3 - Pressure, m; 4 – Motor power, kW; 5 - NPSH, m; 6 – Pressure in the system, at most kgf/cm2; 7 - Liquid density, kg/m3; 8 – Liquid temperature, °C